Title of article
Outdoor polymeric insulators long-term exposed to HVDC
Author/Authors
Sorqvist، نويسنده , , T. Vlastos، نويسنده , , A.E. ، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
8
From page
1041
To page
1048
Abstract
Field experience from outdoor polymeric
insulators exposed to HVDC under natural contamination
conditions is presented. This paper summarizes the peak
leakage current statistics, the hydrophobicity and the surface
material conditions studied by electron spectroscopy
for chemical analysis (ESCA) and attenuated total reflection
Fourier transform infrared (ATR-FTIR) spectroscopy.
The results show a strong interrelation between the
surface conditions and the performance with respect to
leakage currents. Moreover, the results show that the surface
conditions and the performance of the insulators
exposed to HVDC are rather similar to those of the insulators
exposed to WAC.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1997
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399427
Link To Document