Title of article :
The acceleration trend relay for generator stabilization at Colstrip
Author/Authors :
Stigers، نويسنده , , C.A.، نويسنده , , Woods، نويسنده , , C.S.، نويسنده , , Smith، نويسنده , , J.R.، نويسنده , , Setterstrom، نويسنده , , R.D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Pages :
8
From page :
1074
To page :
1081
Abstract :
This paper describes the development and implementation of an acceleration trend relay (ATR) which is currently in operation for generator stabilization at Colstrip Montana. The ATR is unique in that it uses only local signals at the remote generation site to selectively trip generating units based on a real-time assessment of the severity of a disturbance. Local inputs to the ATR are generator shaft speed from magnetic pickups and generator electric power from a watthr transducer. Based on these inputs the appropriate amount of generation to trip i s determined in order to maintain stability of the remaining system. Details on how the device works, how trip decisions are arrived at, and operating experience with the device are presented
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1997
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399431
Link To Document :
بازگشت