    Power differential method for discrimination between fault and magnetizing inrush current in transformers

  • Author/Authors

    Yabe، نويسنده , , K.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    10
  • From page
    1109
  • To page
    1118
  • Abstract
    To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for blocking differential relay in power transformers. However, the second harmonic component in fault current is increased by the introduction of underground 500kV lines. This paper describes a new method to discriminate internal fault from inrush current by the sum of active power flowing into transformers from each terminal. The average power is almost zero for energizing, but an inlernal fault consumes large power. To check the performance of this method, actual inrush current and voltage waveforms of 500/154kV transformer are accurately measured by digital equipment. The usefulness is confirmed by applying the method to the measured inrush and simulated fault data.
  • Keywords
    Transformer protection , Active powerrelays , Magnetizing inrush , Microprocessor-basedrelays , Protection relays