Title of article
Power differential method for discrimination between fault and magnetizing inrush current in transformers
Author/Authors
Yabe، نويسنده , , K.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
10
From page
1109
To page
1118
Abstract
To avoid the needless trip by magnetizing
inrush current, the second harmonic component is commonly
used for blocking differential relay in power transformers.
However, the second harmonic component in fault current is
increased by the introduction of underground 500kV lines.
This paper describes a new method to discriminate internal
fault from inrush current by the sum of active power flowing
into transformers from each terminal. The average power is
almost zero for energizing, but an inlernal fault consumes
large power. To check the performance of this method, actual
inrush current and voltage waveforms of 500/154kV
transformer are accurately measured by digital equipment.
The usefulness is confirmed by applying the method to the
measured inrush and simulated fault data.
Keywords
Transformer protection , Active powerrelays , Magnetizing inrush , Microprocessor-basedrelays , Protection relays