Abstract :
The Hokkaido-Honshu HVDC link
entered service in 1979 for the first phase (150 MW, 125
kV-1200 A) and in 1980 for the second phase (300 MW,
256) kV-1200 A) and has since been operating in good
condition. In the Kamikita converter station situated on
the Honshu side, the thyristor valves for the first and
second phases use 1,344 thyristors rated 4 kV-1.5 kA. To
examine secular changes in the characteristics of
thyristors and estimate their life expectancy, we picked
up eight thyristors from the thyristor valves, measured
main characteristics and compared measurements with
the corresponding values measured before they entered
service. Further, two thyristors were subjected to
temperature and voltage acceleration tests to check for a
change over time of ieakage current. Firom the results of
these investigations it was verified that (he thyristors that
have been in service for 16 years have the characteristics
and service life equivalent to those of the new ones. But
further investigation is required as to the change of turnoff
characteristics.