• Title of article

    Further improvements to a phase-domain ARMA line model in terms of convolution, steady-state initialization, and stability

  • Author/Authors

    Noda، نويسنده , , T.، نويسنده , , Nagaoka، نويسنده , , N.، نويسنده , , Ametani، نويسنده , , A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    8
  • From page
    1327
  • To page
    1334
  • Abstract
    This paper presents further improvements to a phase-domain ARMA (Auto-Regressive Moving Average) line model that is implemented in the ATP version of EMTP. According to the improvement to convolution, each ARMA model, which reproduces the phase-domain frequency dependence of a transmission line, uses its own economical time step considering the frequency characteristic. Linear interpolation is used to allow a different time step for each ARMA model, and this new convolution strategy makes transient calculations more efficient. A steady-state initialization method of the line model is developed, and fault-surge calculations requiring the initialization are demonstrated. Convenient stability criteria of the line model are also presented.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399458