• Title of article

    Dielectric strength of transformer insulation at DC polarity reversal

  • Author/Authors

    Hasegawa، نويسنده , , T.، نويسنده , , Hatano، نويسنده , , M.، نويسنده , , Yamaji، نويسنده , , K.، نويسنده , , Kouan، نويسنده , , T.، نويسنده , , Hosokawa، نويسنده , , N.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    6
  • From page
    1526
  • To page
    1531
  • Abstract
    Among special insulation tests for DC converter transformer, polarity reversal test can be substituted by applied AC voltage test from a stress similarity in oil ducts. In order to investigate equivalent levels of other insulation tests to polarity reversal tests, dielectric strength of transformer at polarity reversals was examined by use of a model of typical oil/paper composite insulation. From comparison of polarity reversal and other insulation tests, it was found that dielectric strength of transformer insulation at polarity reversals is phenomenally similar to that under switching impulse stresses. Equivalent AC test voltage to polarity reversal test was also estimated from the experimental results. The breakdown characteristics of polarity reversal tests showed that partial discharges at polarity reversals impose less harmful stress on insulation barriers than those at usual AC or impulse tests.
  • Keywords
    partial discharge , HVDC , OWpaper insulation , Polarity reversal , Converter transformer
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399487