Abstract
Among special insulation tests for DC
converter transformer, polarity reversal test can be substituted
by applied AC voltage test from a stress similarity in oil ducts.
In order to investigate equivalent levels of other insulation tests
to polarity reversal tests, dielectric strength of transformer at
polarity reversals was examined by use of a model of typical
oil/paper composite insulation.
From comparison of polarity reversal and other insulation
tests, it was found that dielectric strength of transformer
insulation at polarity reversals is phenomenally similar to that
under switching impulse stresses. Equivalent AC test voltage
to polarity reversal test was also estimated from the
experimental results. The breakdown characteristics of
polarity reversal tests showed that partial discharges at
polarity reversals impose less harmful stress on insulation
barriers than those at usual AC or impulse tests.