• Title of article

    A procedure for derating a substation transformer in the presence of widespread electric vehicle battery charging

  • Author/Authors

    Staats، نويسنده , , P.T.، نويسنده , , Grady، نويسنده , , W.M.، نويسنده , , Arapostathis، نويسنده , , A.، نويسنده , , Thallam، نويسنده , , R.S.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    7
  • From page
    1562
  • To page
    1568
  • Abstract
    This paper studies the effect of electric vehcle (EV) battery charging on a substation transformer that supplies commercial, residential, industrial, and EV load on a peak summer day. The analysis begins by modeling non-EV load with typical utility load shapes. EV load is modeled using the results from an analytical solution technique that prehcts the net power and harmonic currents generated by a group of EV battery chargers. We evaluate the amount of transformer derating by maintaining constant daily transformer loss-of-life, with and without EV chargmg. This analysis shows that the time of day and the length of time during which the EVs begin charging are critical in determining the amount of transformer derating required. Our results show that with proper control, EV charging may have very little effect on power system components at the substation level.
  • Keywords
    Electric Vehicles , Transformer Derating , Battery Chargers , Harmonics.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number