Energy absorption of surge arresters on power distribution lines due to direct lightning strokes-effects of an overhead ground wire and installation position of surge arresters
Author/Authors :
Nakada، نويسنده , , K.، نويسنده , , Yokota، نويسنده , , T.، نويسنده , , Yokoyama، نويسنده , , S.، نويسنده , , Asakawa، نويسنده , , A.، نويسنده , , Nakamura، نويسنده , , M.، نويسنده , , Taniguchi، نويسنده , , H.، نويسنده , , Hashimoto، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Pages :
7
From page :
1779
To page :
1785
Abstract :
We describe the characteristics of energy absorption of surge arresters on power distribution lines due to direct lightning strokes. Using the EMTP, the effect of an overhead ground wire and the influence of the installation position of a surge arrester on the energy absorption are investigated quantitatively. The analysis shows that: (1) an overhead ground wire is more effective to prevent damage to surge arresters than increasing the withstand capabilities of surge arresters by a factor of two, (2) the energy absorption without an overhead ground wire is about 3-5 times larger than that with one, and (3) in the case of direct lightning strokes to an overhead ground wire, the energy absorption of surge arresters installed at the termination of a line is approximately 2.3 times larger at maximum than that of arresters installed in the midst ofa line.
Keywords :
lightning , SurgeArrester , Overhead Ground Wire. , Power Distribution Line
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1997
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399496
Link To Document :
بازگشت