• Title of article

    A 12-pulse static synchronous compensator for the distribution system employing the 3-level GTO-inverter

  • Author/Authors

    Hatziadoniu، نويسنده , , C.J.، نويسنده , , Chalkiadakis، نويسنده , , F.E.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    6
  • From page
    1830
  • To page
    1835
  • Abstract
    The paper presents an advanced scheme for the shunt compensation of distribution systems that can significantly improve the harmonic profile of power lines without increasing the system complexity and size. The scheme employs a transformerless arrangement of three-level GTO inverters that can generate a five-level output. A gate control is developed that fully utilizes the capabilities of this arrangement to provide twelve-pulse operation for the compensator. The proposed compensator can connect directly to the distribution grid without a transformer. The effectiveness and performance of the proposed compensator are tested through simulated studies on a 13.8 kV distribution system
  • Keywords
    Static synchronous compensator , three-levelGTO-inverters , Harmonic elimination.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number