Title of article :
Evaluation of service aged 35 kV TR-XLPE URD cables
Author/Authors :
Katz، نويسنده , , C.، نويسنده , , Walker، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Abstract :
This paper provides information on aging of
URD cable insulated with tree-retardant crosslinked polyethylene
(TR-XILPE) compound, installed in a typical utility
environment. Numerous evaluations were performed on
samples of the cables aged up to 7 years in-service. AC and
impulse voltage breakdown data are compared with data for
similar 35 kV ethylene propylene rubber (EPR) and
crosslinked polyethylene (XLPE) insulated cables removed
from the same ultility system. The data show that, to date, the
rate of degradation of TR-XLPE cables is less than that of
the EPR and XliPE insulated cables. Extrapolation of the
data, assuming lhe same rate, indicates TR-XLPE cable will
have the longest life.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY