• Title of article

    Correlation between AC breakdown strength and low frequency dielectric loss of water tree aged XLPE cables

  • Author/Authors

    Hvidsten، نويسنده , , S.، نويسنده , , Ildstad، نويسنده , , E.، نويسنده , , Holmgren، نويسنده , , B.، نويسنده , , Werelius، نويسنده , , P.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    6
  • From page
    40
  • To page
    45
  • Abstract
    This paper describes experiments performed on laboratory aged 12kV and service aged 24 kV XLPE cable samples. Results from measurements of residual ac breakdown strength, degree of water treeing and dissipation factors are presented. The dissipation factor at low frequencies was determined by both time and frequency domain measurements. Relation between these methods are discussed, and it is shown that both can be used for assessing the average ageing state of the cable. The results show that water treeing causes reduced residual ac breakdown strength, high and non-linearly increasing low-frequency dielectric loss.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399513