Title of article
Correlation between AC breakdown strength and low frequency dielectric loss of water tree aged XLPE cables
Author/Authors
Hvidsten، نويسنده , , S.، نويسنده , , Ildstad، نويسنده , , E.، نويسنده , , Holmgren، نويسنده , , B.، نويسنده , , Werelius، نويسنده , , P.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
6
From page
40
To page
45
Abstract
This paper describes experiments performed on laboratory
aged 12kV and service aged 24 kV XLPE cable samples.
Results from measurements of residual ac breakdown
strength, degree of water treeing and dissipation factors are
presented.
The dissipation factor at low frequencies was determined by
both time and frequency domain measurements. Relation
between these methods are discussed, and it is shown that both
can be used for assessing the average ageing state of the cable.
The results show that water treeing causes reduced residual ac
breakdown strength, high and non-linearly increasing low-frequency
dielectric loss.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1998
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399513
Link To Document