The paper presents an original analytical procedure which
enqbles a quick and, for practical purposes sufficiently accurate evaluation
of the significant parts of the ground fault current, for a fault at any of the
towers of a transmission l i e of an arbitrary number of spans. The
advantages of the method are the simplicity and accuracy of the formulae for
solving uniform ladder circuits of any size (from one up to an infinite
number of pis) and any terminal conditions. The formulae are obtained by
applying the "general equations of the line represented by discrete
parameters" on a specific electrical circuit formed by a transmission line
ground wire during ground faults.
The presented method is suitable for analyses aimed at evaluating the
maximum substation grounding system fault current, at selecting the ground
wire capable of withstanding the fault currents and at the prediction of step
and touch voltages near transmission towers.