Title of article :
Harmonic impedance measurement using three-phase transients
Author/Authors :
Nagpal، نويسنده , , M.، نويسنده , , Xu، نويسنده , , W.، نويسنده , , Sawada، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
6
From page :
272
To page :
277
Abstract :
In this paper, a technique is presented for measuring the harmonic impedances of an unbalanced three-phase distribution feeder. The technique uses transients in bus voltages and feeder currents generated by several close-trip operations of the shunt capacitor bank. The work is based on the assumption that the impedance of feeder does not change over time during which the switching operations are performed. Mathematical development of the technique is verified with the laboratory and the field tests. The technique provided good measurements of the harmonic impedances up to 1.5 kHz for the given capacitor sizes. Statistid indices were developed to assess the accuracy of the estimated impedance values.
Keywords :
Feeder load model , harmonic impedance , Transient signalmeasurements.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399544
Link To Document :
بازگشت