Title of article :
On-site partial discharge measurements on premoulded cross-bonding joints of 170 kV XLPE and EPR cables
Author/Authors :
Heizmann، نويسنده , , Th.، نويسنده , , Aschwanden، نويسنده , , Th.، نويسنده , , Hahn، نويسنده , , H.، نويسنده , , Laurent، نويسنده , , M.، نويسنده , , Ritter، نويسنده , , L.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
6
From page :
330
To page :
335
Abstract :
A total number of 15 premoulded joints of three 170 kV cable circuits (XLPE and EPR) were equipped with partial discharge (PD) sensors. The developed sensors are based on inductive high frequency coupling of partial discharge pulses occurring in the joints. The PD activity of each joint was monitored during an after laying AC acceptance test. The test voltage of 190 kV was generated by means of a frequency-tuned seriesresonance test set. The signals of the PD sensors were assessed with a spectrum analyser in a frequency range form 15 to 50 MHz, allowing a good separation of noise from PD signals under high interference levels. The investigation demonstrated the feasibility of on-site PD measurements on joints during after laying tests.
Keywords :
high voltage cable testing. , series-resonance test set , premoulded cablejoints , On-site partial discharge diagnostics