Author/Authors :
Heizmann، نويسنده , , Th.، نويسنده , , Aschwanden، نويسنده , , Th.، نويسنده , , Hahn، نويسنده , , H.، نويسنده , , Laurent، نويسنده , , M.، نويسنده , , Ritter، نويسنده , , L.، نويسنده ,
Abstract :
A total number of 15 premoulded joints of three 170 kV
cable circuits (XLPE and EPR) were equipped with partial
discharge (PD) sensors. The developed sensors are based on
inductive high frequency coupling of partial discharge pulses
occurring in the joints. The PD activity of each joint was monitored
during an after laying AC acceptance test. The test voltage of
190 kV was generated by means of a frequency-tuned seriesresonance
test set. The signals of the PD sensors were assessed with
a spectrum analyser in a frequency range form 15 to 50 MHz,
allowing a good separation of noise from PD signals under high
interference levels. The investigation demonstrated the feasibility of
on-site PD measurements on joints during after laying tests.
Keywords :
high voltage cable testing. , series-resonance test set , premoulded cablejoints , On-site partial discharge diagnostics