Experience with the detection of faulty composite insulators on high-voltage power lines by the electric field measurement method
Author/Authors :
Vaillancourt، نويسنده , , G.H.، نويسنده , , Carignan، نويسنده , , S.، نويسنده , , Jean، نويسنده , , C.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
6
From page :
661
To page :
666
Abstract :
Hydro-Quebec’s experience with polymer insulators began in 1977. A sixteen km section of a 735 kV transmission line near Quebec City was then re-insulated with 282 composite insulators of three different makes in equal proportions. The objective was to study them under real service conditions in order to evaluate their performance and to assess the relative merits of each make. This experimentation was later extended to some other lines and/or voltage levels and has continued up to now. During all these years, various methods of testing composite insulators in-service have been experimented and early in the nineties, the first device developed at IREQ for in-situ testing of porcelain insulators by the electric field method was modified and adapted for use on composite suspension insulators. This paper presents a few cases of insulators having a particularly dangerous type of failure mode and found on the lines by the use of the electric field method. Some background information on the detection of defects by this method is also given and some of the experiments done in the laboratory on composite insulators to define the limits of the method are described.
Keywords :
automatic instrument. , Electric field measurement , hot line test , power transmission lines , Composite insulators , insulator tester , insulator scanner
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399596
Link To Document :
بازگشت