Author/Authors :
Serizawa، نويسنده , , Y.، نويسنده , , Myoujin، نويسنده , , M.، نويسنده , , Kitamura، نويسنده , , K.، نويسنده , , Sugaya، نويسنده , , N.، نويسنده , , Hori، نويسنده , , M.، نويسنده , , Takeuchi، نويسنده , , A.، نويسنده , , Shuto، نويسنده , , I.، نويسنده , , Inukai، نويسنده , , M.، نويسنده ,
Abstract :
As power systems grow larger, it is becoming
difficult to achieve reach and time coordination in backup
protection when using distance relays. To cope with those
problems, current differential backup protection for a busbar and
transmission circuits connected to that busbar on an inter-station
or wide-area basis is proposed. The proposed system can operate
better than conventional systems with respect to operate time,
section selectivity, and so on. A system configuration is also
proposed to utilize ATM transmission networks and time
synchronous systems which make the construction and operation
of the proposed wide-area protection system easy and flexible.
Keywords :
Time synchronization , AM , GPS , backup protection , current differential relay