Title of article :
Two new measuring algorithms for generator and transformer relaying
Author/Authors :
Kasztenny، نويسنده , , B.، نويسنده , , Rosolowski، نويسنده , , E.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
7
From page :
1053
To page :
1059
Abstract :
This paper ]presents new digital measuring algorithms for generator and transformer protection. Two methods are proposed to make the estimation of am litudes of the fundamental frequency component and the higter harmonics immune to frequency deviations. The first method bases on the software re-sampling of the physical data window and on the simultaneous iterative estimation of the frequenc The second algorithm employs the amplitude estimator laving unique frequency response in the entire frequency spectrum and enables direct compensation for the frequency deviations. Also a new Volts/Hertz inverse-time algorithm is proposed which does not call for the direct measure of frequency. It relies on the second method and uses the am litude estimator having the gain close to the inverse of the frequency; therefore, it acts as a direct amplitude-to-frequency estimator. The proposed algorithms were analyzed analytically and tested using EMTP simulations.
Keywords :
digital relayingdigital measurementfrequency deviationpower transformer6 e/ n~e:rcart eolra y
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399650
Link To Document :
بازگشت