Title of article :
AC and switching impulse performance of an ice-covered metal oxide surge arrester
Author/Authors :
Kannus، نويسنده , , K.، نويسنده , , Lahti، نويسنده , , K.، نويسنده , , Nousiainen، نويسنده , , K.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Abstract :
Artificial ice tests were conducted for the first time with a
high voltage metal oxide surge arrester (MOA) consisting of two
units in series. The behaviour of the MOA under glaze ice was
studied with AC voltage and switching impulse current surges. The
AC voltage test results showed that an unevenly ice-coated MOA
may be thermally stressed due to the leakage current transition from
the ice covering of one unit to the interior of another unit not
covered with so much ice. Whether the stressed unit stands up to
this situation or not depends on the thermal properties of the unit
and the duration of the active arcing period. With impulse current
surges the residual voltage across an ice-covered unit may easily
cause a flashover. This leads to a sudden increase in the surge
current. With the MOA studied the current peak was over twice the
value of normal operation, which stressed the lower unit operating
normally.