Title of article
The testing of SF6 generator circuit-breakers
Author/Authors
Smeets، نويسنده , , R.P.P.، نويسنده , , Van der Linden، نويسنده , , W.A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
6
From page
1188
To page
1193
Abstract
Generator circuit-breakers face much higher
current and voltage stress than distribution switchgear. This
has led to a special standard (ANSI C37.013). Strictly in accordance
with this standard’s requirements, test circuits and -
parameters for a 100 kA and 120 kA (25.3 kV) SF, generator
circuit-breaker have been defined. The circuit-breaker is
equipped with capacitors at both sides of the extinction chambers.
The effect of these is to reduce the TRV severity and this
is quantified for the relevant switching duties. Adequate testcircuits
are described. Also, the optional verification of interruption
of generator-fed faults with very large dc components
has been demonstrated. Herein, delayed current zero can
extend arcing time. The importance of arc voltage in reducing
the longer arcing time is illustrated in a calculated example.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1998
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399668