• Title of article

    The testing of SF6 generator circuit-breakers

  • Author/Authors

    Smeets، نويسنده , , R.P.P.، نويسنده , , Van der Linden، نويسنده , , W.A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    6
  • From page
    1188
  • To page
    1193
  • Abstract
    Generator circuit-breakers face much higher current and voltage stress than distribution switchgear. This has led to a special standard (ANSI C37.013). Strictly in accordance with this standard’s requirements, test circuits and - parameters for a 100 kA and 120 kA (25.3 kV) SF, generator circuit-breaker have been defined. The circuit-breaker is equipped with capacitors at both sides of the extinction chambers. The effect of these is to reduce the TRV severity and this is quantified for the relevant switching duties. Adequate testcircuits are described. Also, the optional verification of interruption of generator-fed faults with very large dc components has been demonstrated. Herein, delayed current zero can extend arcing time. The importance of arc voltage in reducing the longer arcing time is illustrated in a calculated example.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399668