    Seismic qualification of transformer high voltage bushings

  • Author/Authors

    Bellorini، نويسنده , , S.، نويسنده , , Salvetti، نويسنده , , M.، نويسنده , , Bettinali، L. نويسنده , , F.، نويسنده , , Zafferani، نويسنده , , G.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    6
  • From page
    1208
  • To page
    1213
  • Abstract
    The paper is born as a contribution to the IEC 36A Working Group 2 “Seismic qualification of bushings” in order to evaluate the coefficients K (amplification factor between the ground and the transformer bushing flange) and R (response factor of the bushing itself) as defined in the IEC 61463 [l]. These coefficients allow the definition of the seismic severity at the flange level to be used for static calculations and vibrational tests on high voltage bushings. For the evaluation of these coefficients both experimental onsite dynamic tests and numerical finite element analyses have been performed for a 160MVA, 2301135kV power transformer [2]. The natural frequencies and the seismic response of the whole transformer (tank, oil conservator and HV bushings), subjected to different earthquakes, have been calculated. At last a comparison between the calculated coefficients (K and R) and those established by the IEC 61463 is illustrated.
  • Keywords
    Finite element method , Time history analysis , Seismicanalysis , Power transformer , Dynamic excitation test , HV bushings , Response spectrum analysis
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number