Title of article :
Effects of topology and feeder capacity on substation distribution transformer loading
Author/Authors :
Tylavsky، نويسنده , , D.J.، نويسنده , , Tatikonda، نويسنده , , N.R.، نويسنده , , Alteneder، نويسنده , , K.، نويسنده , , Brown، نويسنده , , K.E.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Abstract :
As loads on substation distribution transformers
(SDT’s) increase, engineers must decide at what point in time
a second transformer bay needs to be added to keep loss of
load expectation (LOLE) values at acceptable levels. An
alternative to adding an additional transformer bay is to add
ties to physically-close SDT’s to provide backup power on
outage; adding ties improves the SDT LOLE for any given
loading level. Presented in this paper is a method for
assessing the effects of interconnection topology, SDT forced
outage rate (FOR), feeder capacity limitation, and load
duration data on customer reliability. Included in this paper
are the theory and results associated with an application
software program that is being used by utility engineers to
calculate LOLE for an interconnected SDT system.
Keywords :
Substations , Power distribution reliability , powerdistribution planning