Title of article :
Electromagnetic interference from a three phase double circuit 765-kV test line
Author/Authors :
Jeong Boo Kim، نويسنده , , Dong-Il Lee، نويسنده , , Koo Yong Shin، نويسنده , , Hee-Sung Ahn، نويسنده , , Kwang Ho Yang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
6
From page :
266
To page :
271
Abstract :
This paper presents the results of long-term electromagnetic interference (EMI) measurements on the bundle of 6 Cardinal conductors tested at Koreaʹs Kochang 765-kV full-scale test line. The instrumentation and the most important features of the facilities are also described. This new 3-phase double circuit test line can be energized at line-to-line voltages up to 850 kV. The analysis of the data shows that the 6-Cardinal conductor bundle meets the radio and television interference guidelines of the Korea Electric Power Corporation (KEPCO)
Keywords :
Television Interference , Radio Interference , Test Line , E?itra High Voltage , corona