Author/Authors :
Nakiri، نويسنده , , T.، نويسنده , , Maekawa، نويسنده , , Y.، نويسنده , , Takashima، نويسنده , , H.، نويسنده , , Hirotaka Imajo، نويسنده , , T.، نويسنده , , Hirota، نويسنده , , H.، نويسنده , , Ishii، نويسنده , , K.، نويسنده , , Nakao، نويسنده , , Y.، نويسنده , , Shimada، نويسنده , , M.، نويسنده ,
Abstract :
This paper describes the results of a long-term
reliability test of a newly developed 500 kV DC oil-filled cable
and accessories that transmit up to 2800MW. This is the
largest capacity ever used for submarine cables. The test
line was 500m and consist of submarine cables, land cables,
and several kinds of accessories. An optical fiber Sensor was
first installed in the oil duct of the cable to measure the
conductor temperature directly under application of DC
voltage. From 1994 to 1996, we carried out an accelerated
electrical and thermal aging test equivalent to 40 years, a load
cycle test, a polarity reversal test and a transient overloading
current test. Satisfactory breakdown strength was confirmed in
the residual test which followed the long-term test. These
results have been instrumental to the decision to construct
500 kV DC commercial submarine cable lines.
Keywords :
DC power transmission , Underwater cable , Powercable testing , aging , Oil filled cable