Title of article :
Long-term reliability testing of 500 kV DC PPLP-insulated oil-filled cable and accessories
Author/Authors :
Nakiri، نويسنده , , T.، نويسنده , , Maekawa، نويسنده , , Y.، نويسنده , , Takashima، نويسنده , , H.، نويسنده , , Hirotaka Imajo، نويسنده , , T.، نويسنده , , Hirota، نويسنده , , H.، نويسنده , , Ishii، نويسنده , , K.، نويسنده , , Nakao، نويسنده , , Y.، نويسنده , , Shimada، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
8
From page :
319
To page :
326
Abstract :
This paper describes the results of a long-term reliability test of a newly developed 500 kV DC oil-filled cable and accessories that transmit up to 2800MW. This is the largest capacity ever used for submarine cables. The test line was 500m and consist of submarine cables, land cables, and several kinds of accessories. An optical fiber Sensor was first installed in the oil duct of the cable to measure the conductor temperature directly under application of DC voltage. From 1994 to 1996, we carried out an accelerated electrical and thermal aging test equivalent to 40 years, a load cycle test, a polarity reversal test and a transient overloading current test. Satisfactory breakdown strength was confirmed in the residual test which followed the long-term test. These results have been instrumental to the decision to construct 500 kV DC commercial submarine cable lines.
Keywords :
DC power transmission , Underwater cable , Powercable testing , aging , Oil filled cable
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399765
Link To Document :
بازگشت