Author/Authors :
Okabe، نويسنده , , S.، نويسنده , , Koto، نويسنده , , M.، نويسنده , , Teranishi، نويسنده , , T.، نويسنده , , Ishikawa، نويسنده , , M.، نويسنده , , Kobayashi، نويسنده , , T.، نويسنده , , Saida، نويسنده , , T.، نويسنده ,
Abstract :
Authors proposed a simple electric model to simulate the
windings used in gas-insulated shunt reactors up to a high
frequency range. Its applicability was evaluated by comparison
with measurements of the full-scale apparatus model. The
impedance of the high frequency electric model is well simulated
over a frequency range of several kHz to IO MHz.
In this paper, the proposed high frequency electric model was
used for analysis of the re-ignition surges at interruptions of the
reactor of a model substation. The analysis waveform gave a faster
rise and lower peak value than those of the low frequency electric
model, and the cause was clarified.