Abstract :
In 1996, at the Intemational Center for Lightning
Research and Testing (ICLRT) at Camp Blanding, Florida, the
responses of MOV arresters in an unenergized test distribution
system, composed of an overhead line, underground cable, and
padmount transformer with a resistive load, were measured during
very close, direct lightning strikes to the overhead line. Arresters
were installed on the overhead line at two locations 50 m apart (on
either side of the strike point) and at the primary of the padmount
transformer which was connected to the line via the underground
cable. We obtained arrester data for this test configuration from
two lightning flashes (containing a total of five strokes) which were
artificially initiated from a natural thunderstorm, using the rocketand-
wire technique. We present the simultaneously-recorded
arrester discharge current and voltage waveforms from one
lightning stroke for one of the two arresters on the line and for the
arrester at the transfomer primary. Additionally, we estimate the
energy absorbed by the arrester on the line as a function of time for
the first 4 ms of the lightning event. The records presented are
representative of those for all five strokes.