Title of article :
Performance of MOV arresters during very close, direct lightning strikes to a power distribution system
Author/Authors :
Fernandez، نويسنده , , M.I.، نويسنده , , Rambo، نويسنده , , K.J.، نويسنده , , Rakov، نويسنده , , V.A.، نويسنده , , Uman، نويسنده , , M.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
8
From page :
411
To page :
418
Abstract :
In 1996, at the Intemational Center for Lightning Research and Testing (ICLRT) at Camp Blanding, Florida, the responses of MOV arresters in an unenergized test distribution system, composed of an overhead line, underground cable, and padmount transformer with a resistive load, were measured during very close, direct lightning strikes to the overhead line. Arresters were installed on the overhead line at two locations 50 m apart (on either side of the strike point) and at the primary of the padmount transformer which was connected to the line via the underground cable. We obtained arrester data for this test configuration from two lightning flashes (containing a total of five strokes) which were artificially initiated from a natural thunderstorm, using the rocketand- wire technique. We present the simultaneously-recorded arrester discharge current and voltage waveforms from one lightning stroke for one of the two arresters on the line and for the arrester at the transfomer primary. Additionally, we estimate the energy absorbed by the arrester on the line as a function of time for the first 4 ms of the lightning event. The records presented are representative of those for all five strokes.
Keywords :
lightning , MOV Arresters
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399778
Link To Document :
بازگشت