Title of article
Numerical electromagnetic field analysis on measuring methods of tower surge impedance
Author/Authors
Baba، نويسنده , , Y.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1999
Pages
6
From page
630
To page
635
Abstract
The dependence of the tower surge impedance on the
measuring methods is studied with the help of NEG2. The tower
surge impedance measured by the direct method varies dependent
on tho arrangement of the current lead wire. The arrangement of a
vertical current lead wire and a horizontal voltage measuring wire
gives about 20% higher value than that measured with a horizontal
current lead wire in extension to a voltage measuring wire. The
former gives about 150R for a typical double-circuit transmission
tower and it is almost equal to the value given by the estimating
method recommended by the IEEE Working Group. The tower
surge impedance evaluattd from the current splitting ratio at the
tower top is more than 20% higher than that characterized by the
direct method when the current is injected into the connecting point
from a simulated vertical lightning stroke. On the other hand, the
tower surge impedance evaluated by the refraction method is about
10% lower than that characterized by the direct method.
Keywords
Tower surge impedance , Numerical electromagneticfield analysis , Refraction method , Direct method
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1999
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399805