• Title of article

    Numerical electromagnetic field analysis on measuring methods of tower surge impedance

  • Author/Authors

    Baba، نويسنده , , Y.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1999
  • Pages
    6
  • From page
    630
  • To page
    635
  • Abstract
    The dependence of the tower surge impedance on the measuring methods is studied with the help of NEG2. The tower surge impedance measured by the direct method varies dependent on tho arrangement of the current lead wire. The arrangement of a vertical current lead wire and a horizontal voltage measuring wire gives about 20% higher value than that measured with a horizontal current lead wire in extension to a voltage measuring wire. The former gives about 150R for a typical double-circuit transmission tower and it is almost equal to the value given by the estimating method recommended by the IEEE Working Group. The tower surge impedance evaluattd from the current splitting ratio at the tower top is more than 20% higher than that characterized by the direct method when the current is injected into the connecting point from a simulated vertical lightning stroke. On the other hand, the tower surge impedance evaluated by the refraction method is about 10% lower than that characterized by the direct method.
  • Keywords
    Tower surge impedance , Numerical electromagneticfield analysis , Refraction method , Direct method
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1999
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399805