Title of article
Dielectric breakdown strength correlation with time-to-failure during wet aging of XLPE-insulated cables
Author/Authors
Walton، نويسنده , , M.D.، نويسنده , , Bernstein، نويسنده , , B.S.، نويسنده , , Thue، نويسنده , , W.A.، نويسنده , , Smith، نويسنده , , J.T.، نويسنده , , III، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1999
Pages
6
From page
750
To page
755
Abstract
This paper reviews two sets of failure information, the GMTF (a parameter obtained from time-to-failure results) and GMBD stress (a parameter that is calculated from AC breakdown test results), and suggests a correlation. The test results were obtained from accelerated aging experiments on full-sized medium voltage cables in carefully controlled and monitored water-filled tanks. Results show that the ambient temperature AC breakdown strength for equivalently aged cables is influenced primarily by voltage stress during aging-not by the aging temperature. The AC breakdown strength on equivalently aged cables was also shown to decrease with reductions in the aging voltage at all aging temperatures
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1999
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399823
Link To Document