Abstract :
An accurate fault-location algorithm for
two-parallel transmission line of direct ground neutral
system is presented. The algorithm employs the faulted
circuit and healthy circuit of two-parallel line as faultlocation
model, in which remote source impedance is
not involved. It effectively eliminates the effect of load
flow and fault resistance on the accuracy of fault
location. It embodies an accurate location by
measuring only one local end data and it is used in a
procedure that provides the automatic determination of
fault types and phases, rather than requires engineer to
specify them. Simulation results have shown the
effectiveness of the algorithm under the conditions of
non-earth fault (phase-to-phase fault and three-phase
fault with and without earth-connection).