Title of article :
Fault location of two-parallel transmission line for nonearth fault using one-terminal data
Author/Authors :
Zhang Qingchao، نويسنده , , Zhang Yao، نويسنده , , Song Wennan، نويسنده , , Yu Yixin، نويسنده , , Wang Zhigang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
5
From page :
863
To page :
867
Abstract :
An accurate fault-location algorithm for two-parallel transmission line of direct ground neutral system is presented. The algorithm employs the faulted circuit and healthy circuit of two-parallel line as faultlocation model, in which remote source impedance is not involved. It effectively eliminates the effect of load flow and fault resistance on the accuracy of fault location. It embodies an accurate location by measuring only one local end data and it is used in a procedure that provides the automatic determination of fault types and phases, rather than requires engineer to specify them. Simulation results have shown the effectiveness of the algorithm under the conditions of non-earth fault (phase-to-phase fault and three-phase fault with and without earth-connection).
Keywords :
phase-to-phase fault , three-phase fault , two-parallel transmission line , Fault location
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399838