A set of equations is developed in this paper and
used in conjunction with the minimal cut set method [l] to
evaluate the total failure frequency of a parallel redundant
system consisting of series components in each branch where
each component can operate in its wearout period and the
failure rate of each component is not constant. The optimum
maintenance intervals are determined based on the criterion
that the total failure fiequency of the system is minimized.
The Newton-Raphson method is applied to obtain the
unknown optimum maintenance intervals for the system. The
proposed approach is presented and illustrated using a
practical substation example.