Title of article :
Factors affecting the commutation reactance of direct connected generator-converter units
Author/Authors :
Dinh، نويسنده , , Q.N.، نويسنده , , Arrillaga، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
6
From page :
1090
To page :
1095
Abstract :
The effect of generator subtransient reactance, rotor saliency, the number of generators in the Group Connection configuration and adjustable speed operation on the commutation reactance and harmonic levels of direct connected units are examined Restriction limits for firing angles imposed by the commutation angle, generator terminal power factor, equivalent continuous negativesequence harmonic loading are derived that permit the use of n o d generators in direct c o ~ e ~ t uendits without the need for extra harmonic loading capacity. The generator harmonic ratings can be taken at the nominal speed and rated power output.
Keywords :
Unit Connection , Group Connection , HVDC , Converter , Harmonics.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399870