Title of article :
Application and experience with a 15 kV static transfer switch
Author/Authors :
Jipping، نويسنده , , J.E.، نويسنده , , Carter، نويسنده , , W.E.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
5
From page :
1477
To page :
1481
Abstract :
In an effort to dramatically improve rcliability to a sensitivc customcr, Detroit Edison, a DTE Energy Company, installed a 15 kV Static Transfer Switch (STS). This paper presents the background on the clectrical system disturbanccs which had a ncgative impact on an automotive components plant served by Detroit Edison. Previous steps taken, the studies performed, planning considerations, and the most recent actions taken to resolvc the reliability issues are described. In addition, thc performance of the STS during its first year of service is detailed. This application demonstrates that if there is adequate isolation of thc two sources for thc STS, it can avoid disturbances from voltage sags and outages, thus greatly improving ovcrall reliability for the customcr.
Keywords :
Reliability , Power quality , static transfer switch.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399921
Link To Document :
بازگشت