Title of article :
Reducing dead time for single-phase auto-reclosing on a series-capacitor compensated transmission line
Author/Authors :
Tuan Tran-Quoc، نويسنده , , Hadj-Said، نويسنده , , N.، نويسنده , , Sabonnadiere، نويسنده , , J.C.، نويسنده , , Feuillet، نويسنده , , R.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
6
From page :
51
To page :
56
Abstract :
This paper presents a single-phase auto-reclosing study of a 500 kV Vietnamese transmission line. The success of the single-phase auto-reclosing depends on the extinction of the secondary arc. Therefore, the influences of several factors such as shunt and neutral reactors, faulted phase and location, capacitive and inductive coupling and series capacitor discharge on the extinction of secondary arc are investigated. This paper presents the influence of single-phase auto-reclosing on the transient stability of the Vietnam system. A new method in order to reduce the dead time for single-phase auto-reclosing is proposed.
Keywords :
recovery voltage , secondary arc current , stability. , singlephaseauto-reclosing
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2000
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399940
Link To Document :
بازگشت