Title of article :
Disconnector switching in GIS: three-phase testing and phenomena
Author/Authors :
Smeets، نويسنده , , R.P.P.، نويسنده , , van der Linden، نويسنده , , W.A.، نويسنده , , Achterkamp، نويسنده , , M.، نويسنده , , Damstra، نويسنده , , G.C.، نويسنده , , Jean-Luc de Meulemeester، نويسنده , , E.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
Certification tests in accordance with the requirements
of the recent IEC 61259 standard for switching of
bus-charging current by disconnectors of a (three-phase enclosed)
145 kV gas insulated switchgear (GIS) are described. These tests
are primarily aimed at verifying that the discharge between
the disconnector contacts does not introduce internal arc faults.
Special emphasis is given to the high-frequency measuring
system, used to verify a sufficiently severe waveshape of switching
transients in the MHz range. Three-phase tests were performed,
showing phenomena that were not demonstrated in practice
before:
First, it was shown that phase-to-phase voltage transients with
a higher amplitude than the phase-to-ground values do actually
occur. Second, the phase-to-phase capacitive coupling of the busbar
system could raise the trapped charge, left after at the load side of
the installation after disconnection, to values above 1 pu.
In addition, measurements of induced voltages in the secondary
system are reported.
Keywords :
(V)FTO (very) fast transientovervoltages. , disconnectswitches , GIS , Capacitive current switching , Flashover , HF measurement , SF6 , type tests , trapped (residual) charge , prestrike
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY