Measurement of eddy-current loss coefficient PEC-R, derating of single-phase transformers, and comparison with K-factor approach
Author/Authors :
Fuchs، نويسنده , , E.F.، نويسنده , , Yildirim، نويسنده , , D.، نويسنده , , Grady، نويسنده , , W.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
A power amplifier is used to supply sinusoidal currents
of different frequencies for measuring eddy-current losses
of a 25 kVA single-phase transformer under short-circuit condition.
Measured data show that eddy-current loss is a linear function
of frequency with power of 2 and the eddy-current loss coefficient
EC- linear is computed. New measurement techniques
are applied to determine the derating of single-phase transformers
with full-wave diode and thyristor rectifier loads. The derating of
transformers has been defined such that for the (apparent, real)
power transfer of a transformer the total losses are identical to
the rated losses at rated temperature. A relation between apparent
power, derating and K-factor is given taking into account iron-core
and stray-power losses. Measured derating values are compared
with computed results based on the eddy-current losses, iron-core
losses, stray-power losses, and K-factors. The eddy-current loss coefficient
EC- nonlinear is computed from harmonics caused by
diode/thyristor bridge loads.
Keywords :
Eddy-current loss , K-factor , nonlinear load , transformer derating.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY