Title of article :
Factors that influence transformer no-load current harmonics
Author/Authors :
Al-Haj، نويسنده , , A.H.، نويسنده , , El-Amin، نويسنده , , I.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
4
From page :
163
To page :
166
Abstract :
The harmonic components of the no-load current are influenced by many factors. These factors are the flux density, the degree of saturation and the core stacking technique. This paper tested many transformers for the no-load current and its harmonic components. A slight over-excitation results in a substantial increase of the THD level. The increase in the THD is not linear with the flux density. Also this work has demonstrated that having a lower no-load current should not be an indication of lower harmonics. The simulation of the transformer through the use of nonlinear inductors and resistors provided reasonable accuracy.
Keywords :
Harmonics , no-load current , transformer saturation.