Title of article
An experimental thermal siphon bushing
Author/Authors
Daxiong Zeng، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
3
From page
175
To page
177
Abstract
An experimental thermal siphon bushing was constructed
and tested. The thermal siphon was made from the hollow
conductor of a paper-resin bushing with water as heat transport
fluid. The test shows that this bushing has almost uniform temperature
distribution under its critical current and the temperature of
its hottest spot is close to the boiling temperature of water. The current
carrying capacity of this thermal siphon bushing is 50% more
than that of the same bushing without thermal siphon. Simple formulas
are proposed to determine the critical current of a thermal
siphon bushing and estimate the temperature of the hottest spot if
the bushing with thermal siphon is operated above the nameplate
rating.
Keywords
Temperature rise , Condenser bushing , critical current , current carryingcapacity , thermal siphon. , heat run