Title of article :
Repetitive learning control for the correction of wound-type potential transformer measurement errors: sensitivity analysis
Author/Authors :
Hamrita، نويسنده , , T.K.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
6
From page :
461
To page :
466
Abstract :
Successful implementation of a transmission level harmonic measurement system requires accurate and reliable measurement of harmonic voltages and currents. Existing substation instrument transformers are designed for harmonic-free 60 Hz measurements. Hence, their use to measure harmonics leads to the introduction of resonance as well as saturation errors in the measurements. An on-line error correction method to correct for wound-type potential transformer measurement errors has been proposed in previous publications. The error correction was formulated as an output tracking problem where the distorted measurements were used along with the experimentally developed transformer model to reconstruct the transformer input. The scope of this paper is to develop a sensitivity analysis for the error correction method with respect to the transformer parameters. Results of this analysis indicate that the sensitivity of the method with respect to the transformer parameters is quite low.
Keywords :
Correction , sensitivity. , transformer , Error
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2000
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400001
Link To Document :
بازگشت