Author/Authors :
Funabashi، نويسنده , , T.، نويسنده , , Otoguro، Y. نويسنده , , H.، نويسنده , , Mizuma، نويسنده , , Y.، نويسنده , , Dube، نويسنده , , L.، نويسنده , , Ametani، نويسنده , , A.، نويسنده ,
Abstract :
Two new methods are proposed for fault point location
in parallel double-circuit multi-terminal transmission lines by
using voltages and currents information from CCVT’s and CT’s
at all terminal. These algorithms take advantage of the fact that
the sum of currents flowing into a fault section equals the sum of
the currents at all terminals. Algorithm-1 employs an impedance
calculation and Algorithm-2 employs the current diversion ratio
method. Computer simulations are carried out and applications of
the proposed methods are discussed. Both algorithms can be applied
to all types of fault such as phase-to-ground and phase-tophase
faults. As one equation can be used for all types of fault,
classification of fault types and selection of faulted phase are not required.
Phase components of the line impedance are used directly,
so compensation of unbalanced line impedance is not required.
Keywords :
Transmission line , Multi-terminal. , Fault location , Parallel doublecircuit