Title of article :
Efficient reduction of fault current through the grounding grid of substation supplied by cable line
Author/Authors :
Popovic، نويسنده , , L.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
6
From page :
556
To page :
561
Abstract :
The paper presents an analytical procedure suitable for the determination of the part of the ground fault current emanating from the substation grounding grid in the conditions when a particular measure has been taken to reduce it. The practical realization of this measure can be simply described as burying one bare copper wire of a certain length in the same trench as the cable feeding line. In the case of an overhead feeding line the similar measure is denoted in the expert literature as the “counterpoise”. The presented method enables a quick, and, for practical purposes, sufficiently accurate evaluation of the copper wire length providing the maximum possible reduction of the substation grid current. The conveniences of the method result from the simplicity of the formulae for the determination of the realized grid current reduction at the effective copper wire length.
Keywords :
safety conditions. , Ground fault current distribution
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2000
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400016
Link To Document :
بازگشت