Title of article
Observation and analysis of lightning surges at substations connected with UHV designed transmission lines
Author/Authors
Yamada، نويسنده , , T.، نويسنده , , Narita، نويسنده , , T.، نويسنده , , Shioda، نويسنده , , T.، نويسنده , , Okabe، نويسنده , , S.، نويسنده , , Zaima، Susumu نويسنده Tokyo University of Foreign Studies , , E.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
9
From page
675
To page
683
Abstract
On UHV-class transmission lines with sections of
500-kV class insulation, lightning observations have been made
to study the generation and the propagation of overvoltage into
substations. Voltages and currents were recorded at substations
and at junction-tower footings during three flashovers on the
UHV system. These observations were then matched to EMTP
calculations by adjusting the average soil resistivity and the
average conductor height in the propagation model. It is also
found that the attenuation due to corona of voltages was small
because it is expected to be minimal for 8-conductor bundles.
Keywords
Lightning surge , GPS. , UHV , Shielding failure , Lightning observation , EMTP , Substation
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2000