Title of article :
Positional protection of transmission line using fault generated high frequency transient signals
Author/Authors :
Bo، نويسنده , , Z.Q.، نويسنده , , Redfern، نويسنده , , M.A.، نويسنده , , Weller، نويسنده , , G.C.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
This paper presents a new technique for high-speed
protection of transmission lines, the Positional Protection technique.
The technique uses a fault transient detector unit at the
relaying point to capture fault generated high frequency transient
signals contained in the primary currents. The decision to trip is
based on the relative arrival times of these high frequency components
as they propagate through the system. Extensive simulation
studies of technique were carried out to examine the response to
different power system and fault conditions. Results show that the
scheme is insensitive to fault type, fault resistance, fault inception
angle and system source configuration, and that it is able to offer
both very high accuracy and speed in fault detection.
Keywords :
High frequency current signals , positional protection , Transient Based Protection , transmission line protection.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY