Title of article :
Numerical electromagnetic field analysis on lightning surge response of tower with shield wire
Author/Authors :
Baha، نويسنده , , Y.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
6
From page :
1010
To page :
1015
Abstract :
Lightning surge characteristics of a transmission line comprising a tower, a shield wire and phase conductors are studied with the help of NEC-2. A tower struck by a lightning stroke behaves as an antenna until a traveling wave makes several roundtrips in the tower. During this interval, the tower footing impedance appears to be higher than the footing resistance, and the coupling coefficient between a shield wire and a phase conductor is much lower than that in the TEM mode. These affect the estimation of insulator voltages of transmission towers subject to lightning currents having short rise times. On the basis of these findings, the parameters in the multistory tower model, which has been used widely in EMTP multi-conductor analyzes, are newly proposed.
Keywords :
Coupling coefficient , EMTP , numericalelectromagnetic field analysis , tower footing impedance , tower surge impedance. , Lightning surge
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2000
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400073