Title of article :
Numerical electromagnetic field analysis on lightning surge response of tower with shield wire
Author/Authors :
Baha، نويسنده , , Y.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
Lightning surge characteristics of a transmission
line comprising a tower, a shield wire and phase conductors are
studied with the help of NEC-2. A tower struck by a lightning
stroke behaves as an antenna until a traveling wave makes several
roundtrips in the tower. During this interval, the tower footing
impedance appears to be higher than the footing resistance,
and the coupling coefficient between a shield wire and a phase
conductor is much lower than that in the TEM mode. These affect
the estimation of insulator voltages of transmission towers subject
to lightning currents having short rise times. On the basis of these
findings, the parameters in the multistory tower model, which has
been used widely in EMTP multi-conductor analyzes, are newly
proposed.
Keywords :
Coupling coefficient , EMTP , numericalelectromagnetic field analysis , tower footing impedance , tower surge impedance. , Lightning surge
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY