Abstract
The successful implementation of a transmission
level Harmonic Measurement System requires accurate and
reliable measurement of harmonic voltages and currents. Existing
substation instrument transformers are designed for 60 Hz measurements
and they have been shown to cause resonance errors
in the measurements. In this paper, we propose an on-line error
correction method to correct for these resonance errors as well as
possible saturation errors. The error correction is formulated as
an output tracking problem where the distorted measurements
are used along with the experimentally developed transformer
model to reconstruct the transformer input. The method is
generic, thereby permitting its use with any measurement system
that utilizes a transducer with nonideal properties. It is also cost
effective since it can be implemented on a personal computer or
a digital signal processing chip.