Title of article
Negative inductance and numerical instability of the Saturable Transformer Component in EMTP
Author/Authors
Xusheng Chen، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
6
From page
1199
To page
1204
Abstract
Numerical instability of the EMTP built-in model,
the Saturable Transformer Component for the three-winding case,
has been the topic of interest of the EMTP community for the past
twenty years. Through theoretical analysis and computer simulation
the source of the numerical instability of the component is
identified as the use of the negative inductance in the equivalent
circuit of the transformer. A simple modification of the structure of
the component is suggested, and the numerical instability is eliminated.
The modification is supported by theoretical analysis and
verified by the benchmark test of the GPU line energization test
of 1973. The stability of the three-winding transformer equivalent
circuit with a negative inductance is discussed in detail.A topologybased
and duality-derived single-phase three-winding transformer
model is described.