Title of article :
A novel approach to the design of a shunt active filter for an unbalanced three-phase four-wire system under nonsinusoidal conditions
Author/Authors :
Cheng-Che Chen، نويسنده , , Yuan-Yih Hsu، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
A new approach is presented for the design of a shunt
active filter in a three-phase, four-wire distribution system with
unbalanced, distorted sources and unbalanced loads. The purpose
of the shunt active filter is to provide compensation currents
such that the source needs to supply balanced (positive-sequence)
fundamental source current at unity power factor even though
the load consumes harmonic currents as well as positive, negative,
and zero-sequence currents. A major feature of the proposed
approach is that it does not require symmetrical component transformation
to transform the three-phase voltages and currents
to quantities. This makes practical implementation
of the proposed method easier than the symmetrical component
transformation approach. In addition, the power factor of the
positive-sequence fundamental component is close to unity and
only positive-sequence power is supplied by the source. The
effectiveness of the proposed control algorithm is demonstrated
by computer simulation and experimental results of a shunt
active filter for a three-phase four-wire distribution system with
distorted, unbalanced source voltages and unbalanced loads.
Keywords :
unbalanced systems. , three-phase four-wire distributionsystems , Active Power Filter
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY