Miyazaki، نويسنده , , A.، نويسنده , , Takinami، نويسنده , , N.، نويسنده , , Kobayashi، نويسنده , , S.، نويسنده , , Yamauchi، نويسنده , , T.، نويسنده , , Hama، نويسنده , , H.، نويسنده , , Araki، نويسنده , , T.، نويسنده , , Nishima، نويسنده , , H.، نويسنده , , Hata، نويسنده , , H.، نويسنده , , Yamaguchi، نويسنده , , H.، نويسنده ,
Abstract :
This paper reports on the results of a loading current
test and measurements of the line constants of a long-distance
gas-insulated transmission line (GIL) in a tunnel. The loading current
test was carried out at 80% rated current, to verify the soundness
of the thermal expansion and contraction of the GIL. As a result,
the performance of the GIL was confirmed to be appropriate
in terms of the thermal expansion and contraction.With respect to
the line constants and transient enclosure voltage, each of the measured
values was found to be at an appropriate level presenting no
problem for the service operation of this line.
Keywords :
thermal expansion and contraction. , gas-insulated transmission line , Inductance , surge impedance , loading current test , DC resistance , pulse propagation speed , line constant , enclosure voltageunder switching condition , capacitance