Title of article :
A FIRANN as a differential relay for three phase power transformer protection
Author/Authors :
Orille-Fernandez، نويسنده , , A.L.، نويسنده , , Ghonaim، نويسنده , , N.K.I.، نويسنده , , Valencia، نويسنده , , J.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Abstract :
This paper presents an application of a Finite Impulse
Response Artificial Neural Network (FIRANN) as a differential
protection for a real three phase power transformer. Three
FIRANNs are designed, trained and tested. The first one has an
output, which identify internal faults from any other cases like inrush
current and external faults. The two others FIRANNs, each
have two outputs that classify between internal and external faults,
so that, a backup protection is included. These FIRANNs have six
inputs, one for each sampled current signal from both transformer
sides. The sample rate selected is 2 kHz for a 50 Hz power frequency.
All FIRANNs were trained to have a 3.5 ms fault detection
time, which is considered as a very fast protection. The test results
show very good behavior of the FIRANN as a differential protection
and it is planned to build a prototype.
Keywords :
transformerprotection. , digital relays , Artificial neural network
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY