Title of article :
Salt fog testing of polymer housed surge arresters
Author/Authors :
Cherney، نويسنده , , E.A.، نويسنده , , Biglar، نويسنده , , B.، نويسنده , , Jayaram، نويسنده , , S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Pages :
7
From page :
252
To page :
258
Abstract :
This paper deals with the evaluation of the insulation design of polymer housed surge arresters for distribution lines. Five commercial designs were tested in a salt fog chamber for 9 cycles using a cycle consisting of 120 hours of salt fog that was followed by a 48 hour rest period for a total of 1280 hours of salt fog. In these tests, the specification for the 1000-hour salt fog test in IEC 1109 for composite insulators was used as a guide. The results demonstrate that a comprehensive evaluation of the external and internal insulation design of polymer housed surge arresters can be obtained by performing a salt fog test, and as such, the test can be considered as a useful design test. Suggestions for improvements in the insulation design of all polymer housed surge arresters evaluated are given in the paper.
Keywords :
surge arresters. , salt-fog testing , Accelerated aging , polymer housed surge arresters , polymer housings
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2001
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400187
Link To Document :
بازگشت