Author/Authors :
Navaneethan، نويسنده , , S.، نويسنده , , Soraghan، نويسنده , , J.J.، نويسنده , , Siew، نويسنده , , W.H.، نويسنده , , McPherson، نويسنده , , F.، نويسنده , , Gale، نويسنده , , P.F.، نويسنده ,
Abstract :
This paper describes an automatic fault location technique
for permanent faults in Underground Low Voltage Distribution
Networks (ULVDNs). It uses signals from an existing Time
Domain Reflectometry (TDR) instrument. It pre-processes TDR
signals to eliminate reflections due to single-phase tee-offs, and to
locate 3-phase open or short circuit faults and also uses adaptive
filtering to compare the TDR signals to locate faults. In essence,
the procedure minimizes the interpretation skill required from a
user of a typical TDR based fault location instrument. The relative
performance of the system is demonstrated using real field data.
Keywords :
adaptive filtering , Fault location , low voltage distributionnetwork , time domain reflectometry.