The traction power supply system consists of the
feeder, trolley, rails and static conductors. The traction load is
applied between the trolley and rails as a single phase load. In
order to maintain near constant voltage along the traction-route,
the paralleling stations are equipped with auto-transformers
along the track. Further, there are structures such as bridges
and platforms along the traction route. The substation and the
paralleling stations are provided with grounding grids, which are
in turn connected to the static wires. The bridge and the platform
grounds are connected to the rails or static wires. The rails and
the static wires are connected at certain locations to provide
continuity of the return system. The grounding system along the
entire power system is designed so that safety of personnel and
passengers is assured. The performance of the grounding system
is assessed by analysis of the integrated power and grounding
system. The maximum touch voltages at different locations are
computed and compared with the IEEE Standard 80 values to
ensure safety.